The Problem
A property owner in Bournemouth, contacted Greenstar Property Services after their water supplier flagged unusually high consumption, estimating a loss of around 1,000 litres a day. Left unresolved, this level of loss would have added up to roughly 385,000 litres of wasted water a year, along with a significant impact on the customer's bill.
On arrival, our engineer confirmed the water supplier's estimate was accurate, if anything slightly conservative. Measuring the meter over a full 24-hour period showed an actual loss of 1,056 litres, and the dial continued to spin rapidly even with the stopcock closed. This immediately told us two things: the leak was substantial, and it was almost certainly on the incoming mains supply rather than inside the property.


Investigation: Isolating the Fault
Rather than guessing, our engineer began with the step that resolves most leak investigations fastest: isolating whether the fault sat on the internal plumbing or the incoming water supply pipe (WSP). Disconnecting the rising main in the loft and pressure testing it to 3 bar told us everything we needed to know, pressure wouldn't hold above 1.15 bar and dropped instantly the moment the compressor was switched off. This ruled out the water meter and pointed firmly to the mains supply pipe itself.
With the fault located on the WSP, we had a decision to make. Lifting toilets and boxing inside the property would have been disruptive and costly, so instead we chose to expose the pipe at its point of entry outside, revealing 25mm MDPE pipework running underground.
This is where the job got more complicated. A cable avoidance tool (CAT) and signal genny picked up interference from surrounding ground services, making it impossible to trace the exact pipe to run electronically. Rather than excavating blindly along a guessed route, and risk digging up the wrong section, or missing the fault altogether, we switched to a more precise method: tracer gas.
We filled the pipe with a 5% hydrogen-in-nitrogen mix and read concentrations at the surface using a specialist detector. The results were conclusive: readings of over 1,000 ppm in the flowerbed near the boundary, and 850 ppm at the meter box. This narrowed the likely leak point to the boundary line, giving us a precise excavation target rather than a lengthy trench along the entire supply run.
Locating and Confirming the Fault
After clearing overgrown bushes and root growth from the area, we excavated at the boundary and found the source: a joint where the 25mm MDPE pipe adapted to an older ½-inch iron section. With the external stop valve (ESV) turned on, water could be seen visibly pouring from the connection, a clear, confirmed fault rather than a suspected one.
To restore the customer's supply as quickly as possible, our engineer carried out a temporary tightening of the joint. This reduced the flow enough to safely reconnect the system that day, while a permanent repair was scheduled.


The Permanent Repair
On the second visit, the team enlarged the excavation to allow proper access and removed the faulty fitting entirely. Before installing anything new, both sections of pipe, the MDPE and the older iron pipework, were pressure tested independently, holding steady at 2.5 bar and 2.75 bar respectively over a 30-minute test. This confirmed that the leak was isolated to the single failed connection, and that no further faults existed along either section.
A new fitting was installed, the supply reconnected, and air purged from the outlets to clear the system. The meter's central dial, which had been spinning continuously throughout the investigation, sat completely still, visual confirmation that the leak had been fully resolved. The excavation was then backfilled and compacted, with the existing paving and shingles reinstated, so the garden was left as it was found.
The Result
- 1,056 litres a day of water loss identified and stopped
- Equivalent to approximately 385,000 litres a year if left unresolved
- Achieved without excavating the entire supply run, thanks to targeted tracer gas detection
- Supply restored the same day, with a permanent repair completed on a scheduled follow-up visit
This case in Bournemouth Dorset highlights why a methodical, evidence-led approach to leak detection matters. By isolating the fault before digging, and using tracer gas once electronic tracing proved inconclusive, our engineers avoided unnecessary excavation, minimised disruption to the property and garden, and located the fault with pinpoint accuracy.
Greenstar Property Services provides specialist water leak detection, plumbing, heating, drainage and air conditioning services. If you've noticed a spike in your water bill or a supplier warning about high consumption, get in touch — early detection can save thousands of litres a year.